heated sample tube

Electrically heated sampling probe
DSC00425 revised
                                                                                          
Application
Application in extractive sampling systems for cold spots and condensation of the sample to avoid.
Condensation with dust quickly leads to blockage of the gassonde and incorrect displays. This is also by using this approach avoid probe.
An extra filter can be mounted to the probe approach, recommended by dust loads greater than 10 g / m³.
                                                                                             
Description
This approach comes in 3 standard probe lengths: 0.5, 1 and 1.5 meters (other lengths on request).
Optional is a 2-way Modbus / RS485 communication protocol that all possible signals of all installed controllers combines Ankersmid.
 
Series Type AST
AST05x
AST10x
AST15x
AST20x
Temperature sensor
TC Fe-CuNi TC Fe-CuNi
TC Fe-CuNi TC Fe-CuNi
TC Fe-CuNi TC Fe-CuNi
TC Fe-CuNi TC Fe-CuNi
Temperature controller
Microprocessor temperatuur regelaar met alarm (optioneel: RS485 of Modbus) Microprocessor temperature controller with alarm (optional RS485 or Modbus)
Length probe
500mm 500mm
1000mm
1500mm
2000mm
Maximum temperature sampling
500°C 500 ° C
500 ° C
450 ° C
400 ° C
Operating temperature up
200°C 200 ° C
200 ° C
200 ° C
200 ° C
Sample Gas Input:
G3/4"i G3 / 4 "i
Dust Loading
max. 2 g/m3 max 2 g/m3
Probe volume of the tube
200ml/m 200ml / m
Sample pressure max
5 bar g 5 bar g
ambient
-20 °C to +70 °C -20 ° C to 70 ° C
Power supply
230VAC, 500W
115VAC, 500W
230VAC, 800W
115VAC, 800W
1200W 230VAC, 1200W
115VAC, 1200W
1500W 230VAC, 1500W
115VAC, 1500W
Electrical standard
EN 61010, EN60519-1 EN 61010, EN60519-1
Degree of protection
IP54 EN 60529 IP54 EN 60529
Mounting flange
DN65 PN6
Material of parts in contact with the sample
Stainless steel 316 Stainless steel 316

 

 

 

 

 

 
 
 

Documentation

Sample Tubes Download: Sample Tubes

Navigation
Dependences

Language ( English)
Dutch  French 
Translate

Information
Request for informationRequest for information

heated sample tube

address

webmaster
Login